Commission Regulation (EU) No 813/2013Show full title

Commission Regulation (EU) No 813/2013 of 2 August 2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for space heaters and combination heaters (Text with EEA relevance)

 Help about what version

What Version

 Help about advanced features

Advanced Features

More Resources

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

This item of legislation originated from the EU

Legislation.gov.uk publishes the UK version. EUR-Lex publishes the EU version. The EU Exit Web Archive holds a snapshot of EUR-Lex’s version from IP completion day (31 December 2020 11.00 p.m.).

Changes to legislation:

Commission Regulation (EU) No 813/2013, ANNEX III is up to date with all changes known to be in force on or before 15 August 2024. There are changes that may be brought into force at a future date. Changes that have been made appear in the content and are referenced with annotations. Help about Changes to Legislation

Close

Changes to Legislation

Revised legislation carried on this site may not be fully up to date. Changes and effects are recorded by our editorial team in lists which can be found in the ‘Changes to Legislation’ area. Where those effects have yet to be applied to the text of the legislation by the editorial team they are also listed alongside the legislation in the affected provisions. Use the ‘more’ link to open the changes and effects relevant to the provision you are viewing.

View outstanding changes

Changes and effects yet to be applied to the whole legislation item and associated provisions

ANNEX IIIU.K. Measurements and calculations

1.

For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall be made using [F1designated standards], or using other reliable, accurate and reproducible methods that take into account the generally recognised state-of-the-art methods. They shall meet the conditions and technical parameters set out in points 2 to 5.

2.

General conditions for measurements and calculations

(a)

For the purposes of the measurements set out in points 2 to 5, the indoor ambient temperature shall be set at 20 °C ± 1 °C.

(b)

For the purposes of the calculations set out in points 3 to 5, consumption of electricity shall be multiplied by a conversion coefficient CC of 2,5.

(c)

Emissions of nitrogen oxides shall be measured as the sum of nitrogen monoxide and nitrogen dioxide, and expressed in nitrogen dioxide.

(d)

For heaters equipped with supplementary heaters, the measurement and calculation of rated heat output, seasonal space heating energy efficiency, water heating energy efficiency, sound power level and emissions of nitrogen oxides shall take account of the supplementary heater.

(e)

Declared values for rated heat output, seasonal space heating energy efficiency, water heating energy efficiency, sound power level and emissions of nitrogen oxides shall be rounded to the nearest integer.

(f)

Any heat generator designed for a heater, and any heater housing to be equipped with such a heat generator, shall be tested with an appropriate heater housing and heat generator, respectively.

3.

Seasonal space heating energy efficiency of boiler space heaters, boiler combination heaters and cogeneration space heaters

The seasonal space heating energy efficiency ηs shall be calculated as the seasonal space heating energy efficiency in active mode ηson , corrected by contributions accounting for temperature controls, auxiliary electricity consumption, standby heat loss, ignition burner power consumption (if applicable) and, for cogeneration space heaters, corrected by adding the electrical efficiency multiplied by a conversion coefficient CC of 2,5.

4.

Seasonal space heating energy efficiency of heat pump space heaters and heat pump combination heaters

(a)

For establishing the rated coefficient of performance COPrated or rated primary energy ratio PERrated , the sound power level or emissions of nitrogen oxides, the operating conditions shall be the standard rating conditions set out in Table 3 and the same declared capacity for heating shall be used.

(b)

The active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon shall be calculated on the basis of the part load for heating Ph(Tj), the supplementary capacity for heating sup(Tj) (if applicable) and the bin-specific coefficient of performance COPbin(Tj) or bin-specific primary energy ratio PERbin(Tj), weighted by the bin-hours for which the bin conditions apply, using the following conditions:

  • the reference design conditions set out in Table 4;

  • the European reference heating season under average climate conditions set out in Table 5;

  • if applicable, the effects of any degradation of energy efficiency caused by cycling depending on the type of control of the heating capacity.

(c)

The reference annual heat demand QH shall be the design load for heating Pdesignh multiplied by the annual equivalent active mode hours HHE of 2 066.

(d)

The annual energy consumption QHE shall be calculated as the sum of:

  • the ratio of the reference annual heating demand QH and the active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon and

  • the energy consumption for off, thermostat-off, standby, and crankcase heater mode during the heating season.

(e)

The seasonal coefficient of performance SCOP or seasonal primary energy ratio SPER shall be calculated as the ratio of the reference annual heat demand QH and the annual energy consumption QHE .

(f)

The seasonal space heating energy efficiency ηs shall be calculated as the seasonal coefficient of performance SCOP divided by the conversion coefficient CC or the seasonal primary energy ratio SPER, corrected by contributions accounting for temperature controls and, for water-/brine-to-water heat pump space heaters and heat pump combination heaters, the electricity consumption of one or more ground water pumps.

5.

Water heating energy efficiency of combination heaters

The water heating energy efficiency ηwh of a combination heater shall be calculated as the ratio between the reference energy Qref of the declared load profile and the energy required for its generation under the following conditions:

(a)

measurements shall be carried out using the load profiles set out in Table 7;

(b)

measurements shall be carried out using a 24-hour measurement cycle as follows:

  • 00:00 to 06:59: no water draw-off;

  • from 07:00: water draw-offs according to the declared load profile;

  • from end of last water draw-off until 24:00: no water draw-off;

(c)

the declared load profile shall be the maximum load profile or the load profile one below the maximum load profile;

(d)

for heat pump combination heaters, the following additional conditions apply:

  • heat pump combination heaters shall be tested under the conditions set out in Table 3;

  • heat pump combination heaters which use ventilation exhaust air as the heat source shall be tested under the conditions set out in Table 6.

Table 3

Standard rating conditions for heat pump space heaters and heat pump combination heaters

Heat sourceOutdoor heat exchangerIndoor heat exchanger
Inlet dry bulb (wet bulb) temperatureHeat pump space heaters and heat pump combination heaters, except low-temperature heat pumpsLow-temperature heat pumps
Inlet temperatureOutlet temperatureInlet temperatureOutlet temperature
Outdoor air+ 7 °C (+ 6 °C)+ 47 °C+ 55 °C+ 30 °C+ 35 °C
Exhaust air+ 20 °C (+ 12 °C)
Inlet/outlet temperature
Water+ 10 °C/+ 7 °C
Brine0 °C/– 3 °C

Table 4

Reference design conditions for heat pump space heaters and heat pump combination heaters, temperatures in dry bulb air temperature (wet bulb air temperature indicated in brackets)

Reference design temperatureBivalent temperatureOperation limit temperature
Tdesignh Tbiv TOL
– 10 (– 11) °Cmaximum + 2 °Cmaximum – 7 °C

Table 5

European reference heating season under average climate conditions for heat pump space heaters and heat pump combination heaters

binj Tj [°C] Hj [h/annum]
1 to 20– 30 to – 110
21-101
22-925
23-823
24-724
25-627
26-568
27-491
28-389
29-2165
30-1173
310240
321280
332320
343357
354356
365303
376330
387326
398348
409335
4110315
4211215
4312169
4413151
4514105
461574
Total hours:4 910

Table 6

Maximum ventilation exhaust air available [m3/h], at humidity of 5,5 g/m3

Declared load profile XXS XS S M L XL XXL 3XL 4XL
Maximum ventilation exhaust air available1091281281591908701 0212 9438 830

Table 7

Water heating load profiles of combination heaters

h 3XS XXS XS S
Q tap f Tm Q tap f Tm Q tap f Tm Q tap f Tm Tp
kWhl/min°C kWhl/min°C kWhl/min°C kWhl/min°C°C
07:00 0,015225 0,105225 0,105325
07:05 0,015225
07:15 0,015225
07:26 0,015225
07:30 0,015225 0,105225 0,525335 0,105325
07:45
08:01
08:05
08:15
08:25
08:30 0,105225 0,105325
08:45
09:00 0,105225
09:30 0,105225 0,105225 0,105325
10:00
10:30
11:00
11:30 0,015225 0,105225 0,105325
11:45 0,015225 0,105225 0,105325
12:00 0,015225 0,105225
12:30 0,015225 0,105225
12:45 0,015225 0,1052250,525335 0,31541055
14:30 0,015225
15:00 0,015225
15:30 0,015225
16:00 0,015225
16:30
17:00
18:00 0,105225 0,105325
18:15 0,105225 0,105340
18:30 0,015225 0,105225
19:00 0,015225 0,105225
19:30 0,015225 0,105225
20:00 0,105225
20:30 1,05335 0,4241055
20:45 0,105225
20:46
21:00 0,105225
21:15 0,015225 0,105225
21:30 0,015225 0,525545
21:35 0,015225 0,105225
21:45 0,015225 0,105225
Qref 0,345 2,1 2,1 2,1
h M L XL
Q tap f Tm Tp Q tap f Tm Tp Q tap f Tm Tp
kWhl/min°C°C kWhl/min°C°C kWhl/min°C°C
07:00 0,105325 0,105325 0,105325
07:05 1,4640 1,4640
07:15 1,82640
07:26 0,105325
07:30 0,105325 0,105325
07:45 0,105325 4,42101040
08:01 0,105325 0,105325
08:05 3,605101040
08:15 0,105325 0,105325
08:25 0,105325
08:30 0,105325 0,105325 0,105325
08:45 0,105325 0,105325 0,105325
09:00 0,105325 0,105325 0,105325
09:30 0,105325 0,105325 0,105325
10:00 0,105325
10:30 0,10531040 0,10531040 0,10531040
11:00 0,105325
11:30 0,105325 0,105325 0,105325
11:45 0,105325 0,105325 0,105325
12:00
12:30
12:45 0,31541055 0,31541055 0,73541055
14:30 0,105325 0,105325 0,105325
15:00 0,105325
15:30 0,105325 0,105325 0,105325
16:00 0,105325
16:30 0,105325 0,105325 0,105325
17:00 0,105325
18:00 0,105325 0,105325 0,105325
18:15 0,105340 0,105340 0,105340
18:30 0,105340 0,105340 0,105340
19:00 0,105325 0,105325 0,105325
19:30
20:00
20:30 0,73541055 0,73541055 0,73541055
20:45
20:46 4,42101040
21:00 3,605101040
21:15 0,105325 0,105325
21:30 1,4640 0,105325 4,42101040
21:35
21:45
Qref 5,845 11,655 19,07
h XXL 3XL 4XL
Q tap f Tm Tp Q tap f Tm Tp Q tap f Tm Tp
kWhl/min°C°C kWhl/min°C°C kWhl/min°C°C
07:00 0,105325 11,24840 22,49640
07:05
07:15 1,82640
07:26 0,105325
07:30
07:45 6,24161040
08:01 0,105325 5,042425 10,084825
08:05
08:15 0,105325
08:25
08:30 0,105325
08:45 0,105325
09:00 0,105325 1,682425 3,364825
09:30 0,105325
10:00 0,105325
10:30 0,10531040 0,84241040 1,68481040
11:00 0,105325
11:30 0,105325
11:45 0,105325 1,682425 3,364825
12:00
12:30
12:45 0,73541055 2,52321055 5,04641055
14:30 0,105325
15:00 0,105325
15:30 0,105325 2,522425 5,044825
16:00 0,105325
16:30 0,105325
17:00 0,105325
18:00 0,105325
18:15 0,105340
18:30 0,105340 3,362425 6,724825
19:00 0,105325
19:30
20:00
20:30 0,73541055 5,88321055 11,76641055
20:45
20:46 6,24161040
21:00
21:15 0,105325
21:30 6,24161040 12,044840 24,089640
21:35
21:45
Qref 24,53 46,76 93,52

Back to top

Options/Help

Print Options

Close

Legislation is available in different versions:

Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.

Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

See additional information alongside the content

Geographical Extent: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.

Show Timeline of Changes: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.

Close

Opening Options

Different options to open legislation in order to view more content on screen at once

Close

More Resources

Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the EU Official Journal
  • lists of changes made by and/or affecting this legislation item
  • all formats of all associated documents
  • correction slips
  • links to related legislation and further information resources
Close

Timeline of Changes

This timeline shows the different versions taken from EUR-Lex before exit day and during the implementation period as well as any subsequent versions created after the implementation period as a result of changes made by UK legislation.

The dates for the EU versions are taken from the document dates on EUR-Lex and may not always coincide with when the changes came into force for the document.

For any versions created after the implementation period as a result of changes made by UK legislation the date will coincide with the earliest date on which the change (e.g an insertion, a repeal or a substitution) that was applied came into force. For further information see our guide to revised legislation on Understanding Legislation.

Close

More Resources

Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the print copy
  • correction slips

Click 'View More' or select 'More Resources' tab for additional information including:

  • lists of changes made by and/or affecting this legislation item
  • confers power and blanket amendment details
  • all formats of all associated documents
  • links to related legislation and further information resources