Commission Regulation (EU) 2016/1388 of 17 August 2016 establishing a Network Code on Demand Connection (Text with EEA relevance)

 Help about what version

What Version

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

This item of legislation originated from the EU

Legislation.gov.uk publishes the UK version. EUR-Lex publishes the EU version. The EU Exit Web Archive holds a snapshot of EUR-Lex’s version from IP completion day (31 December 2020 11.00 p.m.).

Status:

This is the original version as it was originally adopted in the EU.
This legislation may since have been updated - see the latest available (revised) version

ANNEX I Frequency ranges and time periods referred to in Article 12(1)

Synchronous areaFrequency rangeTime period for operation
Continental Europe47,5 Hz-48,5 HzTo be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz30 minutes
Nordic47,5 Hz-48,5 Hz30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 30 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz30 minutes
Great Britain47,0 Hz-47,5 Hz20 seconds
47,5 Hz-48,5 Hz90 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz90 minutes
51,5 Hz-52,0 Hz15 minutes
Ireland and Northern Ireland47,5 Hz-48,5 Hz90 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz90 minutes
Baltic47,5 Hz-48,5 HzTo be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 HzTo be specified by each TSO, but not less than 30 minutes

The table shows the minimum time periods for which a transmission-connected demand facility, a transmission-connected distribution facility or a distribution system has to be capable of operating on different frequencies, deviating from a nominal value, without disconnecting from the network.

ANNEX II Voltage ranges and time periods referred to in Article 13(1)

Synchronous areaVoltage rangeTime period for operation
Continental Europe0,90 pu-1,118 puUnlimited
1,118 pu-1,15 puTo be specified by each TSO but not less than 20 minutes and not more than 60 minutes
Nordic0,90 pu-1,05 puUnlimited
1,05 pu-1,10 pu60 minutes
Great Britain0,90 pu-1,10 puUnlimited
Ireland and Northern Ireland0,90 pu-1,118 puUnlimited
Baltic0,90 pu-1,118 puUnlimited
1,118 pu-1,15 pu20 minutes

The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network where the voltage base for pu values is at or above 110 kV and up to (not including) 300 kV.

Synchronous areaVoltage rangeTime period for operation
Continental Europe0,90 pu-1,05 puUnlimited
1,05 pu-1,10 puTo be specified by each TSO but not less than 20 minutes and not more than 60 minutes
Nordic0,90 pu-1,05 puUnlimited
1,05 pu-1,10 puTo be specified by each TSO but not more than 60 minutes
Great Britain0,90 pu-1,05 puUnlimited
1,05 pu-1,10 pu15 minutes
Ireland and Northern Ireland0,90 pu-1,05 puUnlimited
Baltic0,90 pu-1,097 puUnlimited
1,097 pu-1,15 pu20 minutes

The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network, where the voltage base for pu values is from 300 kV to 400 kV (including).

Back to top

Options/Help

Print Options

Close

Legislation is available in different versions:

Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.

Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

Opening Options

Different options to open legislation in order to view more content on screen at once

Close

More Resources

Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the EU Official Journal
  • lists of changes made by and/or affecting this legislation item
  • all formats of all associated documents
  • correction slips
  • links to related legislation and further information resources
Close

More Resources

Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the print copy
  • correction slips

Click 'View More' or select 'More Resources' tab for additional information including:

  • lists of changes made by and/or affecting this legislation item
  • confers power and blanket amendment details
  • all formats of all associated documents
  • links to related legislation and further information resources