Commission Delegated Regulation (EU) No 811/2013 of 18 February 2013 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to the energy labelling of space heaters, combination heaters, packages of space heater, temperature control and solar device and packages of combination heater, temperature control and solar device (Text with EEA relevance)
When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.
Legislation.gov.uk publishes the UK version. EUR-Lex publishes the EU version. The EU Exit Web Archive holds a snapshot of EUR-Lex’s version from IP completion day (31 December 2020 11.00 p.m.).
Version Superseded: 31/12/2020
Point in time view as at 31/01/2020.
There are currently no known outstanding effects for the Commission Delegated Regulation (EU) No 811/2013, ANNEX V.
Revised legislation carried on this site may not be fully up to date. At the current time any known changes or effects made by subsequent legislation have been applied to the text of the legislation you are viewing by the editorial team. Please see ‘Frequently Asked Questions’ for details regarding the timescales for which new effects are identified and recorded on this site.
For space heaters, the technical documentation referred to in Article 3(1)(c) shall include:
the name and address of the supplier;
a description of the space heater model sufficient for its unambiguous identification;
where appropriate, the references of the harmonised standards applied;
where appropriate, the other technical standards and specifications used;
the identification and signature of the person empowered to bind the supplier;
technical parameters:
for boiler space heaters and cogeneration space heaters, the technical parameters set out in Table 7, measured and calculated in accordance with Annex VII;
for heat pump space heaters, the technical parameters set out in Table 8, measured and calculated in accordance with Annex VII;
for heat pump space heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;
any specific precautions that shall be taken when the space heater is assembled, installed or maintained.
For combination heaters, the technical documentation referred to in Article 3(2)(c) shall include:
the name and address of the supplier;
a description of the combination heater model sufficient for its unambiguous identification;
where appropriate, the references of the harmonised standards applied;
where appropriate, the other technical standards and specifications used;
the identification and signature of the person empowered to bind the supplier;
technical parameters:
for boiler combination heaters, the technical parameters set out in Table 7, measured and calculated in accordance with Annex VII;
for heat pump combination heaters, the technical parameters set out in Table 8, measured and calculated in accordance with Annex VII;
for heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;
any specific precautions that shall be taken when the combination heater is assembled, installed or maintained.
Technical parameters for boiler space heaters, boiler combination heaters and cogeneration space heaters
a High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet. | ||||||||
b Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet). | ||||||||
Model(s): [information identifying the model(s) to which the information relates] | ||||||||
Condensing boiler: [yes/no] | ||||||||
Low-temperatureb boiler: [yes/no] | ||||||||
B11 boiler: [yes/no] | ||||||||
Cogeneration space heater: [yes/no] | If yes, equipped with a supplementary heater: [yes/no] | |||||||
Combination heater: [yes/no] | ||||||||
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
---|---|---|---|---|---|---|---|---|
Rated heat output | Prated | x | kW | Seasonal space heating energy efficiency | ηs | x | % | |
For boiler space heaters and boiler combination heaters: Useful heat output | For boiler space heaters and boiler combination heaters: Useful efficiency | |||||||
At rated heat output and high-temperature regimea | P4 | x,x | kW | At rated heat output and high-temperature regimea | η4 | x,x | % | |
At 30 % of rated heat output and low-temperature regimeb | P1 | x,x | kW | At 30 % of rated heat output and low-temperature regimeb | η1 | x,x | % | |
For cogeneration space heaters: Useful heat output | For cogeneration space heaters: Useful efficiency | |||||||
At rated heat output of cogeneration space heater with supplementary heater disabled | PCHP100+Sup0 | x,x | kW | At rated heat output of cogeneration space heater with supplementary heater disabled | ηCHP100+Sup0 | x,x | % | |
At rated heat output of cogeneration space heater with supplementary heater enabled | PCHP100+Sup100 | x,x | kW | At rated heat output of cogeneration space heater with supplementary heater enabled | ηCHP100+Sup100 | x,x | % | |
For cogeneration space heaters: Electrical efficiency | Supplementary heater | |||||||
At rated heat output of cogeneration space heater with supplementary heater disabled | ηel,CHP100+Sup0 | x,x | % | Rated heat output | Psup | x,x | kW | |
At rated heat output of cogeneration space heater with supplementary heater enabled | ηel,CHP100+Sup100 | x,x | % | Type of energy input | ||||
Auxiliary electricity consumption | Other items | |||||||
At full load | elmax | x,x | kW | Standby heat loss | Pstby | x,x | kW | |
At part load | elmin | x,x | kW | Ignition burner power consumption | Pign | x,x | kW | |
In standby mode | PSB | x,xxx | kW | Annual energy consumption | QHE | x | kWh or GJ | |
Sound power level, indoors | LWA | x | dB | |||||
For combination heaters: | ||||||||
Declared load profile | Water heating energy efficiency | ηwh | x | % | ||||
Daily electricity consumption | Qelec | x,xxx | kWh | Daily fuel consumption | Qfuel | x,xxx | kWh | |
Annual electricity consumption | AEC | x | kWh | Annual fuel consumption | AFC | x | GJ | |
Contact details | Name and address of the supplier. |
Technical parameters for heat pump space heaters and heat pump combination heaters
a For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). | ||||||||
b If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9. | ||||||||
Model(s): [information identifying the model(s) to which the information relates] | ||||||||
Air-to-water heat pump: [yes/no] | ||||||||
Water-to-water heat pump: [yes/no] | ||||||||
Brine-to-water heat pump: [yes/no] | ||||||||
Low-temperature heat pump: [yes/no] | ||||||||
Equipped with a supplementary heater: [yes/no] | ||||||||
Heat pump combination heater: [yes/no] | ||||||||
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application. | ||||||||
Parameters shall be declared for average, colder and warmer climate conditions. | ||||||||
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
---|---|---|---|---|---|---|---|---|
Rated heat output a | Prated | x | kW | Seasonal space heating energy efficiency | ηs | x | % | |
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj | Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj | |||||||
Tj = – 7 °C | Pdh | x,x | kW | Tj = – 7 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = + 2 °C | Pdh | x,x | kW | Tj = + 2 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = + 7 °C | Pdh | x,x | kW | Tj = + 7 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = + 12 °C | Pdh | x,x | kW | Tj = + 12 °C | COPd or PERd | x,xx or x,x | – or % | |
Tj = bivalent temperature | Pdh | x,x | kW | Tj = bivalent temperature | COPd or PERd | x,xx or x,x | – or % | |
Tj = operation limit temperature | Pdh | x,x | kW | Tj = operation limit temperature | COPd or PERd | x,xx or x,x | – or % | |
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | Pdh | x,x | kW | For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | COPd or PERd | x,xx or x,x | – or % | |
Bivalent temperature | Tbiv | x | °C | For air-to-water heat pumps: Operation limit temperature | TOL | x | °C | |
Cycling interval capacity for heating | Pcych | x,x | kW | Cycling interval efficiency | COPcyc or PERcyc | x,xx or x,x | – or % | |
Degradation co-efficientb | Cdh | x,x | — | Heating water operating limit temperature | WTOL | x | °C | |
Power consumption in modes other than active mode | Supplementary heater | |||||||
Off mode | POFF | x,xxx | kW | Rated heat outputb | Psup | x,x | kW | |
Thermostat-off mode | PTO | x,xxx | kW | |||||
Standby mode | PSB | x,xxx | kW | Type of energy input | ||||
Crankcase heater mode | PCK | x,xxx | kW | |||||
Other items | ||||||||
Capacity control | fixed/variable | For air-to-water heat pumps: Rated air flow rate, outdoors | — | x | m3/h | |||
Sound power level, indoors/outdoors | LWA | x / x | dB | For water- or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger | — | x | m3/h | |
Annual energy consumption | QHE | x | kWh or GJ | |||||
For heat pump combination heater: | ||||||||
Declared load profile | x | Water heating energy efficiency | ηwh | x | % | |||
Daily electricity consumption | Qelec | x,xxx | kWh | Daily fuel consumption | Qfuel | x,xxx | kWh | |
Annual electricity consumption | AEC | x | kWh | Annual fuel consumption | AFC | x | GJ | |
Contact details | Name and address of the supplier. |
For temperature controls, the technical documentation referred to in Article 3(3)(b) shall include:
the name and address of the supplier;
a description of the temperature control model sufficient for its unambiguous identification;
where appropriate, the references of the harmonised standards applied;
where appropriate, the other technical standards and specifications used;
the identification and signature of the person empowered to bind the supplier;
technical parameters:
the class of the temperature control;
the contribution of the temperature control to seasonal space heating energy efficiency in %, rounded to one decimal place;
any specific precautions that shall be taken when the temperature control is assembled, installed or maintained.
For solar devices, the technical documentation referred to in Article 3(4)(b) shall include:
the name and address of the supplier;
a description of the solar device model sufficient for its unambiguous identification;
where appropriate, the references of the harmonised standards applied;
where appropriate, the other technical standards and specifications used;
the identification and signature of the person empowered to bind the supplier;
technical parameters (for pumps in the collector loop if applicable):
the collector aperture area Asol in m2, to two decimal places;
the collector efficiency ηcol in %, rounded to the nearest integer;
the energy efficiency class of the solar hot water storage tank, determined in accordance with point 3 of Annex II;
the standing loss S of the solar hot water storage tank in W, rounded to the nearest integer;
the storage volume V of the solar hot water storage tank in litres and m3;
the annual non-solar heat contribution Qnonsol in kWh in terms of primary energy for electricity and/or in kWh in terms of GCV for fuels, for the load profiles M, L, XL and XXL under average climate conditions, rounded to the nearest integer;
the pump power consumption solpump in W, rounded to the nearest integer;
the standby power consumption solstandby in W, to two decimal places;
the annual auxiliary electricity consumption Qaux in kWh in terms of final energy, rounded to the nearest integer;
any specific precautions that shall be taken when the solar device is assembled, installed or maintained.
For packages of space heater, temperature control and solar device, the technical documentation referred to in Article 3(5)(c) shall include:
the name and address of the supplier;
a description of the package of space heater, temperature control and solar device model sufficient for its unambiguous identification;
where appropriate, the references of the harmonised standards applied;
where appropriate, the other technical standards and specifications used;
the identification and signature of the person empowered to bind the supplier;
technical parameters:
the seasonal space heating energy efficiency in %, rounded to the nearest integer;
the technical parameters set out in points 1, 3 and 4 of this Annex;
any specific precautions that shall be taken when the package of space heater, temperature control and solar device is assembled, installed or maintained.
For packages of combination heater, temperature control and solar device, the technical documentation referred to in Article 3(6)(c) shall include:
the name and address of the supplier;
a description of the package of combination heater, temperature control and solar device model sufficient for its unambiguous identification;
where appropriate, the references of the harmonised standards applied;
where appropriate, the other technical standards and specifications used;
the identification and signature of the person empowered to bind the supplier;
technical parameters:
the seasonal space heating energy efficiency and water heating energy efficiency in %, rounded to the nearest integer;
the technical parameters set out in points 2, 3 and 4 of this Annex;
any specific precautions that shall be taken when the package of combination heater, temperature control and solar device is assembled, installed or maintained.
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.
Point in Time: This becomes available after navigating to view revised legislation as it stood at a certain point in time via Advanced Features > Show Timeline of Changes or via a point in time advanced search.
Geographical Extent: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.
Show Timeline of Changes: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
This timeline shows the different versions taken from EUR-Lex before exit day and during the implementation period as well as any subsequent versions created after the implementation period as a result of changes made by UK legislation.
The dates for the EU versions are taken from the document dates on EUR-Lex and may not always coincide with when the changes came into force for the document.
For any versions created after the implementation period as a result of changes made by UK legislation the date will coincide with the earliest date on which the change (e.g an insertion, a repeal or a substitution) that was applied came into force. For further information see our guide to revised legislation on Understanding Legislation.
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: